CENSEO FIELD TEST REPORT — SUMMARY
Continental House Condominium · Unit 606

All tap test sessions · Jeanette Hesedahl, PE · CENSEO AV+Acoustics
All AIIC values below are minimum values — flanking was not fully evaluated in any test. Actual performance may be higher once flanking paths are accounted for.
The green-highlighted row is the underlayment recommended by the audio engineer.

All Test Results

Table 1. Combined Acoustical Test Results — All Sessions
Report # Date Source Room Receiver Room Flooring Configuration Field AIIC Note
Session 1 · Test #26035-01 · May 7, 2026
26035-01 May 7, 2026 #606 Living #506 Living / Dining / Kitchen 5/8″ Oak Engineered Wood on Eclipse II (0.070″ EVA foam) 51
Session 2 · Test Session #P26035A · May 18, 2026
26035A-02 May 18, 2026 #606 Living #506 Living / Dining / Kitchen 5/8″ Oak Engineered Wood on 6mm Quiet Board 49
26035A-03 May 18, 2026 #606 Den #506 Den 5/8″ Oak Engineered Wood on 3mm Quiet Walk * 51

* 26035A-03: Receiver room volume (660 cu. ft.) is below the ASTM minimum of 1,412 cu. ft. — result should be interpreted with caution.

Full Test Reports